HVO vs. Fossil Diesel on a Data Center Backup Diesel Engine: Field Test Results and Lifecycle GHG Assessment
June 30, 2026
This report presents results from a field emissions test of HVO versus fossil diesel conducted on May 6, 2026, on a 2 MW Cummins QSK60 Series backup diesel engine (model DQKAB) at a Compass Datacenters facility in Texas. Testing was performed by Mostardi Platt using United States Environmental Protection Agency reference methods at two load conditions, 50% and 100% of rated capacity, for each fuel.